Category List
-
- Power Semiconductors
-
- LED Lighting
-
- Power Supply Unit
-
- Industry Control & Protection
-
- Circuit Breakers
-
- Interface Components
-
- Power Modules & Bridges
-
- Vacuum Contactor
-
-
- Switches & Switchgears
-
- More

Search Catalog

What's New

>> Contact Information
GREEGOO Electric Co.,Ltd.
No.6 Floor,Jinye Mansion, Lvzhuang, Liushi, Yueqing, Zhejiang, 325604 P.R. China
Tel: +86-577-62776000
Mob: +86-159 5877 6000
Fax: +86-577-62776006
E-mail: Peter@greegoo.com
Skype: greegoo_peter
MSN: greegoo_peter@hotmail.com
Visit us on the web at...
http://www.greegoo.com
You are here: Home >> Products >> Vacuum Contactor >> Vacuum Circuit Breakers (VCB) >> ZW32-400A/630A 12kV
ZW32-400A/630A 12kV
|
Vacuum Circuit Breakers (ZW32-12 outdoor type)
|
Summarize
|
|
ZW832-12 series pole outdoor vacuum circuit breaker is outdoor high voltage switch equipment with rated voltage 12KV, tri-phase AC 50Hz, which is mainly applicable to breaking, Switch-off on load current, overload current, short-circuit current of urban network, rural network system
|
Main technical specifications:
|
|
Type
|
Unit
|
ZW32-12/
T400-12.5
|
ZW32-12/
T630-16
|
ZW32-12/
T630-20
|
|
rated voltage
|
KA
|
12
|
|
rated current
|
A
|
400
|
630
|
630
|
|
rated short circuit breaking current
|
KA
|
12.5
|
16
|
20
|
|
rated short circuit switch-off on curretn)speak vavue)
|
31.5
|
40
|
50
|
|
rated peak withstand current
|
31.5
|
40
|
50
|
|
rated short circuit withstand current
|
12.5
|
16
|
20
|
|
rated short circuit lasting time
|
S
|
4
|
|
Rated insulating level
|
lighting impulse withstand voltage (peak value)
|
KV
|
of pole, earthing 75, breaking fracture 85
|
|
1 min P.F withstand voltage
|
of ple earthing42 , braking fractrue 48
|
|
rated operating sequence
|
|
break-0.3s-close and break-180s-close and break(electric operating mechanism)
|
|
rated short circuit curretn breaking time
|
Time
|
30
|
|
mechanical endurance
|
10000
|
|
rated operating voltage (opening, closing coil)
|
v
|
DC220,110,ac220
|
|
permit abrasion total thickness of dynamic and static contactor
|
mm
|
3
|
|
rated curretn of loading unlocking device
|
A
|
5
|
|
curretn transformer curretn ratio
|
|
200/5? 400/5? 600/5
|
|
opening distance of contact
|
mm
|
9+1
|
|
over travel of contact
|
2+0.5
|
|
average switch-off speed?
|
m/s
|
1.2+0.3
|
|
average switch-on speed
|
0.+0.2
|
|
switch-off time
|
ms
|
30~60
|
|
switch-on time
|
20~40
|
|
bounce time of switch-on
|
≤2
|
|
same period of three phase switch-off on
|
≤2
|
|
each phase feedback DC resistance
|
μΩ
|
≤80
|
|
energy storing motor
|
rated voltage
|
V
|
-220
|
|
rated power
|
W
|
200
|
|
energy storing time
|
S
|
≤8
|
|
quality
|
Kg
|
85
|
|
|