Industrial DIN Rail Power Supplies(120W Single Output)
- Universal AC input / full range - Protections: Short circuit/ Over load/ Over voltage/Over temperature - Cooling by free air convection - Can be installed on DIN rail TS-35/7.5 or 15 - LED indicator for power on - 100% full load burn-in test - Fixed switch frequency at 55KHz - 3 years warranty - Dimensions: 65.5*125.2*100mm (W*H*D)
Model
HDR-120-12
HDR-120-24
HDR-120-48
Output
DC Voltage
12V
24V
48V
Voltage Tolerance
+2%
+1%
+1%
Rated Current
10A
5A
2.5A
Current Range
76W
76.8W
76.8W
Rated Power
0-10A
0-10A
0-2.5A
Ripple & Noise
80mVp-p
80mVp-p
100mVp-p
DC Adjustment Range
12-14V
24-28V
48-53V
Setup, Rise, Hold Time
500ms,70ms/230VAC at full load500ms,70ms/115VA Cat full load
Hold Time
36ms/230VAC32ms/115VAC at full load
Input
Voltage Range
88~132 VAC/176~264VAC47~63 Hz;selected by 248~370VDC
AC Current
2.6 A/115 V 1.6A/ 230 V
Efficiency
80%
84%
85%
Inrush Current
Cold start 20A/115V 40A/230V
Leakage Current
<3.5mA/240VAC
Protection
Over Load
105%~150%
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage
120%~135%
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMP.
85℃+5℃(TSW1)
90℃+5℃(TSW1)
90℃+5℃(TSW1)
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
Environment
Working Temp & Humidity
-10℃~+60℃;20%~90 %RH
Storage Temp &Humidity
-20℃~+85℃;10%~95 %RH
Vibration
10~500Hz,2G 10min./1cycle, period for 60min, each along X, Y, Z axes
Safety
Withstand Voltage
I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC
Isolation Resistance
I/P-O/P, I/P-FG, O/P-FG: 100MΩ / 500VDC
Standards
Safety Standard
Design refer to UL508,UL60950-1,TUV EN60950-1
EMC Standard
Design refer to EN55011,EN55022,EN61000-3-2,-3, EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2