12KV 1600A 2000A 2500A Vacuum Contactor

Home Products Vacuum ContactorMedium Voltage Vacuum Contactor (7.2/12kV)12KV 1600A 2000A 2500A Vacuum Contactor

12KV 1600A 2000A 2500A Vacuum Contactor
12KV 1600A 2000A 2500A Vacuum Contactor
Product details

12KV 1600A 2000A 2500A Vacuum Contactor

The Greegoo GC24-12kV Series AC high-voltage vacuum contactor stands out in the 12kV market with its exceptional high-current ratings of 1600A, 2000A, and 2500A, enabling robust handling of demanding loads like large motors, transformers, and capacitor banks.

Technical highlights

Technical Highlights

Ratings: Rated working voltage of 12kV, with currents of 1600A, 2000A, and 2500A; rated breaking capacity of 5kA; short-circuit time of 4s.

Endurance: Mechanical life of 10,000 cycles (latching device replacement required every 100,000 operations for mechanically latched models); electrical life of 25,000 cycles (AC3) and 10,000 cycles (AC4).

Operating Frequency: 120 cycles/hour; mechanical latching at 30 cycles/hour.

Control Power: Electrical holding (starting <1500W, holding <300W); mechanical holding (closing <1600W, opening <700W).

Insulation: Power frequency withstand voltage of 42kV, lightning impulse withstand voltage of 75kV (peak).

These features ensure excellent switching characteristics, long service life, high safety, and reliability, making it suitable for demanding applications.

Specification
Performance Parameter Units GC24-12/1600 GC24-12/2000 GC24-12/2500
Rated Working Voltage (Ur) kV 12 12 12
Rated Working Current (Ie) A 1600 2000 2500
Rated Making Capacity (Im) kA 6.3 6.3 6.3
Rated Breaking Capacity (Ic) kA 5 5 5
Rated Overcurrent Withstand Capacity kA/s 12/1 15/1 18/1
Rated Short-Time Withstand Current (Ik) kA 6.3 6.3 6.3
Rated Peak Withstand Current (Ip) kA 16 16 16
Rated Short-Circuit Time (tk) s 4 4 4

 

Rated Insulation Level

 
Parameter Type Sub-Parameter Units Value

Rated

Power Frequency Withstand Voltage

Vacuum break kV 42
Phase to phase kV 42
Phase-to-Earth kV 42

Rated

Lightning Impulse Withstand Voltage

(Peak)

Vacuum break kV 75
Phase to phase kV 75
Phase-to-Earth kV 75

 

Additional Operating and Endurance Parameters

 
Parameter Units GC24-12/1600 GC24-12/2000 GC24-12/2500 Notes
Main Circuit Contact Resistance μΩ ≤80 ≤50 ≤60 -
Rated Operating Frequency cycles/hour 120 120 120 -
Mechanical Latching Operating Frequency cycles/hour 30 30 30 -
Mechanical Endurance (Mechanical Life) cycles 10,000 10,000 10,000

For mechanically latched models,

replace the latching device

every 100,000 operations.

Electrical Endurance (Electrical Life) - AC3 cycles 25 25 25

Making current: 4kA,

Breaking current: 2.5kA.

Electrical Endurance (Electrical Life) - AC4 cycles 10 10 10

Making current: 4kA,

Breaking current: 4kA.

Control and Auxiliary Circuits

Control Circuit

Rated Voltage (Ua): AC & DC 110V, 220V, or customized according to user requirements.

Control Power:

Electrical Holding: Starting <1500W; Holding <300W.

Mechanical Holding: Closing <1600W; Opening <700W.

Auxiliary Circuit

Quantity: Up to 8 combinations of NO (Normally Open) and NC (Normally Closed) contacts; 6 combinations for mechanical holding type; 10 combinations for models using electronic control modules.

Rated Conventional Thermal Current: AC380V 6A; AC220V 10A.

Auxiliary Contact Rated Making & Breaking Current: AC380V 6A, AC220V 6A, DC220V 0.5A.

Power Frequency Withstand Voltage: 2kV (excluding components).

Operating Characteristics

Opening and Closing Time: Closing time ≤120ms; Opening time ≤80ms.

Three-phase Synchronization: ≤2ms.

Minimum Pickup Voltage: ≤85% Ua; Maximum Drop-out Voltage = 10%~75% Ua.

 
Electric holding and mechanical latching diagram

electric holding vacuum contactor 12kv 2500a

 

 


 

mechanical latching type of 12kv 2500a vacuum contactor

Dimensions

EVC24-12/2500 vacuum contactor