Overload
The instruments are designed to withstand 1.2 times rated current and voltage for 2 hours, Ammeters are also designed for 10 times rated current and voltmeters and frequency meters for 2 times rated voltage for 0.5 seconds
Dielectric Test:
All meters are designed to 2kv AC RMS for 1 minute
Environment:
The meters are suitable to work between-10℃ to 60℃ with relative humidity upto 90% these meters can be calibrated at other temperaturesk if required on request
Damping time:
lessthan 3 seconds
Mounting Clamps:
Mounting clamps are provided to fix the meter flush type on panel