Manual Motor Starter (EGV2-ME)

Standard power ratings of 3-phase motors 50/60Hz in category AC-3 Setting range of thermal trips (A) Magnetic tripping current (A) Thermal current Ie in (A) Reference
220V 230V (kW) 400V 415V (kW) 440V (kW) 550V (kW) 690V (kW)
- - - - - 0.1-0.16 1.5 0.16 EGV2-ME01
- 0.06 0.06 - - 0.16-0.25 2.4 0.25 EGV2-ME02
0.06 0.09 0.09 - - 0.25-0.40 5 0.4 EGV2-ME03
- 0.12 0.18 - 0.37 0.40-0.63 8 0.63 EGV2-ME04
0.09 0.25 0.25 0.37 0.55 0.63-1 13 1 EGV2-ME05
0.18 0.37 0.37 0.37 0.75 1-1.6 22.5 1.6 EGV2-ME06
0.37 0.75 0.75 1.1 1.5 1.6-2.5 33.5 2.5 EGV2-ME07
.0.55 1.1 1.5 1.5 2.2 2.5-4 51 4 EGV2-ME08
1.1 22 2.2 3 4 4-6.3 78 6.3 EGV2-ME10
1.5 3 4 4 5.5 6-10 138 9 EGV2-ME14
2.2 5.5 5.5 7.5 9 9-14 170 13 EGV2-ME16
4 7.5 7.5 9 15 13-18 223 17 EGV2-ME20
5.5 9 11 11 18.5 17-23 327 21 EGV2-ME21
5.5 11 11 15 22 20-25 327 23 EGV2-ME22
7.5 15 15 18.5 22 24-32 416 30 EGV2-ME32